SunSynk with a generator battery capped#
Introduction#
I had an issue where I had a generator added to my SunSynk inverter, however when I ran the generator, the batteries would not charge past 2KW, instead of the full 5.5KW that the generator produced.

I knew it had to be a setting as on solar, the batteries charge past 5KW.
Setup#
Tap on the Gear Icon on the top right.

Tap on the Battery icon

Note
Use this formula to find a safe starting current: 10A = +-500W
Info
So if you have a 5KW generator, set the value to 99A
Tap the block next to “Gen Charge” to put a tick in the block. The first block next to amps that was greyed out will now turn white. Tap in this block to change the value. Press the up button to increase this value. Click on “OK” to Apply.
